Mountains

Carnes

   Only Nature Moves and Conditions Air Better!

 

    Home    About Carnes    General Literature    Employment    Contact Us   

Fire Dampers > Low Leakage Smoke Dampers

Class I and II Low Leakage Smoke Dampers

Smoke dampers are intended for installation in ducts and air transfer openings that are designed to resist the passage of air and smoke.  The dampers are installed to operate automatically, controlled by a smoke detection system and are capable of being positioned from a remote command station.  Smoke dampers can be used in HVAC systems where the fans are shut down in the event of a fire, and can also be used in smoke control systems designed to operate during a fire incident.

Carnes smoke dampers are UL and ULC listed, and are available with Class I (ES series) or Class II (ET series) leakage ratings.  Class I smoke dampers provide a maximum leakage of 8 cfm per square foot at 4.0 inches static pressure.  Class II smoke dampers provide a maximum leakage of 20 cfm per square foot at 4.0 inches static pressure.  Smoke dampers are designed to be installed in a vertical or horizontal mounting position in the ductwork or a separate sleeve within 24" of the smoke partition.

Carnes ES and ET series smoke dampers are approved for use in engineered smoke control systems and are controlled via a smoke detection system.  Numerous accessories are available with smoke dampers, including transitions, side plates, damper sleeves, remote control boxes and smoke detectors.  Electric or pneumatic actuators are available for operating Carnes smoke dampers.

Class I

Model ESWA - Class I Low Leakage smoke damper, crimped 3V blade

Model ESYA - Class I Low Leakage smoke damper, airfoil blade

Model ESZA - Class I Low Leakage smoke damper, true round

Class II

Model ETWA - Class II Low Leakage smoke damper, crimped 3V blade

Model ETYA - Class II Low Leakage smoke damper, airfoil blade

Model ETZA - Class II Low Leakage smoke damper, true round